Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Line monitoring
■ Overview
■ Benefits • Can be used without auxiliary voltage in any network from 160 to 600 V AC worldwide thanks to wide voltage range • Variably adjustable to overvoltage, undervoltage or range monitoring • Freely configurable delay times and RESET response • Width 22.5 mm • Permanent display of ACTUAL value and network fault type on the digital versions • Automatic correction of the direction of rotation by distinguishing between power system faults and wrong phase sequence • All versions with removable terminals • All versions with screw terminals or alternatively with innovative spring-type terminals
■ Application SIRIUS 3UG46 15 monitoring relay
Solid-state line monitoring relays provide maximum protection for mobile machines and plants or for unstable networks. Network and voltage faults can be detected early and rectified before far greater damage ensues.
The relays are used above all for mobile equipment, e.g. air conditioning compressors, refrigerating containers, building site compressors and cranes. Function
Application
Phase sequence
• Direction of rotation of the drive
Phase failure
• A fuse has tripped
Phase asymetry is evaluated as the difference between the greatest and the smallest phase voltage relative to the greatest phase voltage. Undervoltage or overvoltage exists when at least one phase voltage deviates by 20 % from the set rated system voltage or the directly set limit values are overshot or undershot. The rms value of the voltage is measured. With the 3UG46 17 or 3UG46 18 relay, a wrong direction of rotation can also be corrected automatically.
• Failure of the control supply voltage • Broken cable Phase asymmetry
• Overheating of the motor due to asymmetrical voltage • Detection of asymmetrically loaded networks
Undervoltage
• Increased current on a motor with corresponding overheating • Unintentional resetting of a device • Network collapse, particularly with battery power
Overvoltage
• Protection of a plant against destruction due to overvoltage
■ Technical specifications The 3UG45 11 phase sequenced relay monitors the phase sequence in a three-phase network. No adjustments are required for operation. The device has an internal power supply and works using the closed-circuit principle. If the phase sequence at the terminals L1-L2-L3 is correct, the output relay picks up after the delay time has elapsed and the LED is lit. If the phase sequence is wrong, the output relay remains in its rest position. Note: When one phase fails, connected loads (motor windings, lamps, transformers, coils, etc.) create a voltage at the terminal of the failed phase due to the network coupling. Because the 3UG45 11 relays are not resistant to voltage , such a phase failure is not detected. Should this be required, then the 3UG45 12 monitoring relay must be used.
Correct phase sequence
L1-L2-L3 11/14 ON
11/12
21/24 21/22
NSB0_01565a
3UG45 11 monitoring relays
Wrong phase sequence
L3-L2-L1 11/14 OFF 11/12
21/24 21/22
8/62
Siemens IC 10 · 2011
NSB0_01566a
8
Depending on the version, the relays monitor phase sequence, phase failure with and without N conductor monitoring, phase asymetry, undervoltage or overvoltage.
© Siemens AG 2010
Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Line monitoring 3UG45 12 monitoring relays
3UG45 13 monitoring relays
The 3UG45 12 line monitoring relay monitors three-phase networks with regard to phase sequence, phase failure and phase unbalance of 10 %. Thanks to a special measuring method, a phase failure is reliably detected in spite of the wide voltage range from 160 to 690 V and through the load of up to 90 %. The device has an internal power supply and works using the closed-circuit principle. No adjustments are required. When the mains voltage is switched on, the green LED is lit. If the phase sequence at the terminals L1-L2-L3 is correct, the output relay picks up. If the phase sequence is wrong, the red LED flashes and the output relay remains in its rest position. If a phase fails, the red LED is permanently lit and the output relay drops.
The 3UG45 13 line monitoring relay monitors three-phase networks with regard to phase sequence, phase failure, phase asymetry and undervoltage of 20 %. The device has an internal power supply and works using the closed-circuit principle. The hysteresis is 5 %. The integrated response delay time is adjustable from 0 to 20 s and responds to undervoltage. If the direction is incorrect, the device switches off immediately. Thanks to a special measuring method, a phase failure is reliably detected in spite of the wide voltage range from 160 to 690 V and through the load of up to 80 %. When the mains voltage is switched on, the green LED is lit. If the phase sequence at the terminals L1-L2-L3 is correct, the output relay picks up. If the phase sequence is wrong, the red LED flashes and the output relay remains in its rest position. If a phase fails, the red LED is permanently lit and the output relay drops.
Note: The red LED is a fault diagnostic indicator and does not show the current relay status. The 3UG45 12 monitoring relay is suitable for line frequencies of 50/60 Hz. Phase failure
Note: The red LED is a fault diagnostic indicator and does not show the current relay status. The 3UG45 13 monitoring relay is suitable for line frequencies of 50/60 Hz. Phase failure and undervoltage
L1-L2-L3
L2-L3
L1-L2-L3 L1-L2-L3 3~
11/14 11/12
L2-L3
Hysteresis 5%
L1-L2-L3 -20 %
n
21/24 21/22 LED rd
11/12
8
NSB0_01567a
11/14
21/24 21/22
OFF
ON Phase loss
NSB0_01569a
LED rd
OFF
OFF
Wrong phase sequence
ON Phase loss
OFF Delay
ON
OFF
Wrong phase sequence L3-L2-L1 11/14
L3-L2-L1
11/12
21/24 21/22 LED rd OFF FLASH OFF Phase sequence
11/12 NSB0_01570a
NSB0_01568a
11/14
21/24 21/22 LED rd OFF FLASH OFF Phase sequence
Siemens IC 10 · 2011
8/63
© Siemens AG 2010
Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Line monitoring 3UG46 14 monitoring relays
3UG46 15/ 3UG46 16 monitoring relays
The 3UG46 14 line monitoring relay has a wide voltage range and an internal power supply. The device is equipped with a display and is parameterized using three buttons. It monitors threephase networks with regard to phase asymetry from 5 to 20 %, phase failure, undervoltage and phase sequence. The hysteresis is adjustable from 1 to 20 V. In addition the device has a response delay and ON-delay from 0 to 20 s in each case. The integrated response delay time responds to phase asymetry and undervoltage. If the direction is incorrect, the device switches off immediately. Thanks to a special measuring method, a phase failure is reliably detected in spite of the wide voltage range from 160 to 690 V and through the load of up to 80%.
The 3UG46 15/3UG46 16 line monitoring relay has a wide voltage range and an internal power supply. The device is equipped with a display and is parameterized using three buttons. The 3UG46 15 device monitors three-phase networks with regard to phase failure, undervoltage, overvoltage and phase sequence. The 3UG46 16 monitoring relay monitors the neutral conductor as well. The hysteresis is adjustable from 1 to 20 V. In addition the device has two separately adjustable delay times for overvoltage and undervoltage from 0 to 20 s in each case. If the direction is incorrect, the device switches off immediately. Thanks to a special measuring method, a phase failure is reliably detected in spite of the wide voltage range from 160 to 690 V and through the load of up to 80 %.
The 3UG46 14 monitoring relay can be operated on the basis of either the open-circuit or closed-circuit principle and with manual or auto RESET.
The 3UG46 15/ 3UG46 16 monitoring relay can be operated on the basis of either the open-circuit or closed-circuit principle and with manual or auto RESET.
Wrong phase sequence
Wrong phase sequence
L3-L2-L1
L3-L2-L1
11/14
11/14
11/12
11/12
21/24 21/22
21/24 21/22
Phase failure
Phase failure L2-L3
L1-L2-L3
L1-L2-L3 L2-L3 L1-L2-L3-N L1-L2-L3
11/14
L1-L2-L3 L1-L2-L3-N
11/14
11/12
11/12
NSB0_01576a
21/24 21/22
NSB0_01572a
8
L1-L2-L3
21/24 21/22
Undervoltage
Undervoltage
x-y
<
Hysteresis
x-y
11/14
Hysteresis
<
11/14
11/12
21/22
NSB0_01573a
NSB0_01577a
11/12
21/24
21/24 21/22 Delay
Delay
onDelay
Overvoltage > Asy 0%
Hysteresis 2%
11/14
11/12
11/12 NSB0_01578a
11/14
21/24 21/22 onDelay
Siemens IC 10 · 2011
Delay
Hysteresis
< x-y
NSB0_01574a
Unbalance
8/64
NSB0_01571a
With the closed-circuit principle selected
NSB0_01571a
With the closed-circuit principle selected
21/24 21/22 Delay
© Siemens AG 2010
Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Line monitoring Undervoltage Hysteresis
<
x-y
11/14 11/12 50 ms
NSB0_01588a
The 3UG46 17/ 3UG46 18 line monitoring relay has an internal power supply and can automatically correct a wrong direction of rotation. Thanks to a special measuring method, a phase failure is reliably detected in spite of the wide voltage range from 160 to 690 V AC and through the load of up to 80 %. The device is equipped with a display and is parameterized using three buttons. The 3UG46 17 line monitoring relay monitors three-phase networks with regard to phase sequence, phase failure, phase unbalance, undervoltage and overvoltage. The 3UG46 18 monitoring relay monitors the neutral conductor as well. The hysteresis is adjustable from 1 to 20 V. In addition the device has delay times from 0 to 20 s in each case for overvoltage, undervoltage, phase failure and phase unbalance. The 3UG46 17/ 3UG46 18 monitoring relay can be operated on the basis of either the open-circuit or closed-circuit principle and with manual or auto RESET. The one changeover is used for warning or disconnection in the event of power system faults (voltage, unbalance), the other responds only to a wrong phase sequence. In conjunction with a or reversing assembly it is thus possible to change the direction automatically.
21/24 21/22 Delay
Overvoltage >
Hysteresis
x-y
11/14 11/12 50 ms
With the closed-circuit principle selected
21/24
Phase failure
21/22
NSB0_01589a
3UG46 17/ 3UG46 18 monitoring relays
Delay
L1-L2-L3 L1-L2-L3-N
L2-L3 L1-L2-L3 L1-L2-L3 L1-L2-L3-N
Unbalance > Asy 0%
11/14 11/12
11/14
NSB0_01587a
11/12
8
21/22
50 ms
NSB0_01590a
50 ms 21/24
Hysteresis 2%
21/24 21/22 Delay
Type
3UG45 11 ... 3UG45 13, 3UG46 14 ... 3UG46 18
General data Rated insulation voltage Ui Pollution degree 3 Overvoltage category III acc. to EN 60664-1
V
690
Rated impulse withstand voltage
kV
6
Load capacity of the output relay • Conventional thermal current Ith
A
5
Rated operational current Ie at • AC-15/24 ... 400 V • DC-13/24 V • DC-13/125 V • DC-13/250 V
A A A A
3 1 0.2 0.1
Minimum load at 17 V DC
mA
5
Electrical endurance AC-15
Million oper- 0.1 ating cycles
Mechanical endurance
Million oper- 10 ating cycles
Control circuit
Circuit diagrams 3UG45 11-.A, 3UG45 12-.A
3UG45 11-.B, 3UG45 12-.B, 3UG45 13, 3UG46 14, 3UG46 15, 3UG46 17
L1 L2 L3 N
L1 L2 L3
L1 L2 L3 L1 L2 L3
11
NSB0_01537a
L1 L2 L3
11
21
3UG4
3UG4 12 14
Note: It is not necessary to protect the measuring circuit for device protection. The protective device for line protection depends on the cross-section used.
3UG46 16, 3UG46 18
NSB0_01536a
N L1 L2 L3
11
21
3UG4 12 14 22 24
NSB0_01538a
12 14 22 24
Siemens IC 10 · 2011
8/65
© Siemens AG 2010
Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Line monitoring
■ Selection and ordering data PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 101
3UG45 11-1AP20 Hysteresis Undervoltage detection
3UG46 15-1CR20
3UG46 17-1CR20
3UG46 16-1CR20
OverON-delay Tripping voltage delay detection
Version of Rated control auxiliary supply voltage s Us1)
DT
3UG46 18-1CR20
Order No. s
3UG45 11-2BP20 DT
Screw terminals
Price per PU
3UG45 12-2BR20
Spring-type terminals
Order No.
s
CO
V
--
1 2
160 … 260 AC
A A
3UG45 11-1AN20 3UG45 11-1BN20
B B
3UG45 11-2AN20 3UG45 11-2BN20
1 2
320 … 500 AC
A A
3UG45 11-1AP20 3UG45 11-1BP20
A B
3UG45 11-2AP20 3UG45 11-2BP20
1 2
420 … 690 AC
B B
3UG45 11-1AQ20 3UG45 11-1BQ20
B B
3UG45 11-2AQ20 3UG45 11-2BQ20
A A
3UG45 12-1AR20 3UG45 12-1BR20
A A
3UG45 12-2AR20 3UG45 12-2BR20
A
3UG45 13-1BR20
A
3UG45 13-2BR20
A
3UG46 14-1BR20
A
3UG46 14-2BR20
3UG46 15-1CR20
A
3UG46 15-2CR20
3UG46 16-1CR20
A
3UG46 16-2CR20
3UG46 17-1CR20
B
3UG46 17-2CR20
3UG46 18-1CR20
B
3UG46 18-2CR20
Price per PU
Monitoring of phase sequence Auto-RESET --
--
--
--
Monitoring of phase sequence, phase failure and phase unbalance Auto-RESET, closed-circuit principle, unbalance threshold 10 %
8
--
--
--
--
--
1 2
160 … 690 AC
Monitoring of phase sequence, phase failure, unbalance and undervoltage Analogically adjustable, Auto-RESET, closed-circuit principle, fixed unbalance threshold 20 % 5 % of set value
✓
--
--
0.1 … 20
2
160 … 690 AC
Digitally adjustable, auto or manual RESET, open-circuit or closed-circuit principle, unbalance threshold 0 or 5 ... 20 % Adjustable ✓ 1 ... 20 V
--
0.1 ... 20
0.1 … 20
2
160 … 690 AC
Monitoring of phase sequence, phase failure, overvoltage and undervoltage Digitally adjustable, Auto-RESET or manual RESET, open-circuit or closed-circuit principle Adjustable ✓ 1 ... 20 V
✓
--
0.1 … 202)
22)
160 … 690 AC
A
Monitoring of phase sequence, phase and N conductor failure, overvoltage and undervoltage Digitally adjustable, Auto-RESET or manual RESET, open-circuit or closed-circuit principle Adjustable ✓ 1 ... 20 V
✓
--
0.1 … 202)
22)
90… 400 AC against N
A
Automatic correction of the direction of rotation in case of wrong phase sequence, phase failure, phase unbalance, overvoltage and undervoltage Digitally adjustable, auto or manual RESET, open-circuit or closed-circuit principle, unbalance threshold 0 or 5 ... 20 % Adjustable ✓ 1 ... 20 V
✓
--
0.1 … 20
23)
160 … 690 AC
A
Automatic correction of the direction of rotation in case of wrong phase sequence, phase and N conductor failure, phase unbalance, overvoltage and undervoltage Digitally adjustable, auto or manual RESET, open-circuit or closed-circuit principle, unbalance threshold 0 or 5 ... 20 % Adjustable ✓ 1 ... 20 V
✓
--
0.1 … 20
23)
90… 400 AC against N
A
✓ Function available -- Function not available 1)
Absolute limit values.
2)
1 CO each and 1 tripping delay time each for Umin and Umax.
3)
1 CO each for power system fault and phase sequence correction.
For accessories, see page 8/90.
8/66
Siemens IC 10 · 2011
* You can order this quantity or a multiple thereof. Illustrations are approximate
© Siemens AG 2010
Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Voltage monitoring
■ Overview
■ Benefits • Versions with wide voltage supply range • Variably adjustable to overvoltage, undervoltage or range monitoring • Freely configurable delay times and RESET response • Width 22.5 mm • Display of ACTUAL value and status messages • All versions with removable terminals • All versions with screw terminals or alternatively with innovative spring-type terminals
■ Application • Protection of a plant against destruction due to overvoltage • Switch-on of a plant at a defined voltage and higher • Protection against overloaded control supply voltages, particularly with battery power • Threshold switch for analog signals from 0.1 to 10 V SIRIUS 3UG46 31 monitoring relay
The relays monitor single-phase AC voltages (rms value) and DC voltages against the set threshold value for overshoot and undershoot. The devices differ with regard to their power supply (internal or external).
■ Technical specifications
The operating and measuring range extends from 17 to 275 V AC/DC. The threshold values for overshoot or undershoot can be freely configured within this range. If one of these threshold values is reached, the output relay responds according to the set principle of operation as soon as the tripping delay time has elapsed. This delay time UDel can be set from 0.1 to 20 s like the ON-delay time onDel. The hysteresis is adjustable from 0.1 to 150 V. The device can be operated on the basis of either the open-circuit or closed-circuit principle and with manual or auto RESET. One output changeover is available as signaling .
A1-A2 =
< Hysteresis
=0
NSB0_01585a
The 3UG46 33 voltage monitoring relay has an internal power supply and performs overshoot, undershoot or range monitoring of the voltage depending on how it is parameterized. The device is equipped with a display and is parameterized using three buttons.
8
Undervoltage
3UG46 33 monitoring relays
11/14 11/12 onDelay
Delay
Range monitoring
With the closed-circuit principle selected A1-A2 =
Overvoltage
<
>
Hysteresis A1-A2 =
Hysteresis
>
Hysteresis NSB0_01584a
=0 11/14 11/12 onDelay
NSB0_01586a
=0 11/14 11/12 onDelay
Delay
Delay =
Delay
Delay
Delay
Siemens IC 10 · 2011
8/67
© Siemens AG 2010
Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Voltage monitoring Undervoltage
The 3UG46 31/3UG46 32 voltage monitoring relay is supplied with an auxiliary voltage of 24 V AC/DC or 24 to 240 V AC/DC and performs overshoot, undershoot or range monitoring of the voltage depending on how it is parameterized. The device is equipped with a display and is parameterized using three buttons. The measuring range extends from 0.1 to 60 V or 10 to 600 V AC/DC. The threshold values for overshoot or undershoot can be freely configured within this range. If one of these threshold values is reached, the output relay responds according to the set principle of operation as soon as the delay time has elapsed. This delay time UDel can be set from 0.1 to 20 s. The hysteresis can be set from 0.1 to 30 V or 0.1 to 300 V. The device can be operated on the basis of either the open-circuit or closed-circuit principle and with manual or auto RESET. One output changeover is available as signaling .
A1-A2 < Hysteresis =0 NSB0_01582a
3UG46 31/ 3UG46 32 monitoring relays
11/14 11/12 Delay
Range monitoring A1-A2
With the closed-circuit principle selected Overvoltage
>
<
A1-A2
Hysteresis > Hysteresis
11/14
NSB0_01581a
=0 11/14 11/12
NSB0_01583b
Hysteresis
11/12 Delay
Delay =
Delay
Delay
8
Delay
3UG46 31
3UG46 32
3UG46 33
General data Rated insulation voltage Ui Pollution degree 3 Overvoltage category III acc. to EN 60664-1
V
690
Rated impulse withstand voltage Uimp
kV
6
Permissible measuring range single-phase AC/DC voltage
V
0.1 … 68
10 … 650
17 … 275
Setting range single-phase voltage
V
0.1 ... 60
10 ... 600
17 ... 275
Measuring frequency
Hz
40 ... 500
Load capacity of the output relay • Conventional thermal current Ith
A
5
Rated operational current Ie at • AC-15/24 ... 400 V • DC-13/24 V • DC-13/125 V • DC-13/250 V
A A A A
3 1 0.2 0.1
Minimum load at 17 V DC
mA
5
Measuring circuit
Control circuit
Circuit diagrams 3UG46 31-.AA30, 3UG46 32-.AA30
AC/DC
3UG46 31-.AW30, 3UG46 32-.AW30
ULoad
A1(+) IN(+)
AC/DC 11
3UG46 33
AC/DC
ULoad
A1(+) IN(+)
11
12 14
NSB0_01532b
8/68
Siemens IC 10 · 2011
A1(+)
A2(–) NSB0_01533b
11 12 14
Note: It is not necessary to protect the measuring circuit for device protection. The protective device for line protection depends on the cross-section used.
© Siemens AG 2010
Monitoring Relays SIRIUS 3UG Monitoring Relays for Stand-Alone Installation Voltage monitoring
■ Selection and ordering data • • • •
Digitally adjustable, with illuminated LC display Auto or manual RESET Open or closed-circuit principle 1 CO
3UG46 31-1AA30
3UG46 33-2AL30
Measuring range
Hysteresis
Rated control supply voltage Us
V
V
V
PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 101
DT
DT
Screw terminals Order No.
Price per PU
Spring-type terminals Order No.
Price per PU
Internal power supply without auxiliary voltage, ON-delay and tripping delay can be adjusted separately 0.1 ... 20 s 17 … 275 AC/DC
0.1 ... 150
17 … 275 AC/DC1)
A
3UG46 33-1AL30
A
3UG46 33-2AL30
Supplied from an external auxiliary voltage, tripping delay adjustable 0.1 ... 20 s 0.1 … 60 AC/DC 10 … 600 AC/DC
0.1 ... 30 0.1 ... 300
24 AC/DC
A A
3UG46 31-1AA30 3UG46 32-1AA30
B B
3UG46 31-2AA30 3UG46 32-2AA30
0.1 … 60 AC/DC 10 … 600 AC/DC
0.1 ... 30 0.1 ... 300
24 … 240 AC/DC
A A
3UG46 31-1AW30 3UG46 32-1AW30
B B
3UG46 31-2AW30 3UG46 32-2AW30
Absolute limit values.
8
1)
For accessories, see page 8/90.
* You can order this quantity or a multiple thereof. Illustrations are approximate
Siemens IC 10 · 2011
8/69